Sample report · fictitious flat

Flat 602, Green Arcade, Pune

Green Arcade is a fictitious project and every name, number and reading on this page is a worked example. The layout, the grading and the wording are exactly what you receive.

Flat
2BHK resale
Findings
5
Before purchase
1
Booking
SS-8K2Q-602

1 · Summary

Two sources need action before registration and move-in.

Most likely sources: bathroom floor waterproofing in the flat above, window frame sealing, a concealed drain joint, the balcony floor slope, and condensation in one closed corner.

Book an Inspection
Floor sketch, Flat 602N ↑
Floor sketch with findings pinnedLIVINGBEDROOM 2KITCHENBEDROOM 1BATHSHAFTBATH 2PASSAGEBALC12345
1 Repair before purchase3 Repair before use1 Monitor

2 · Findings

Five findings, room by room.

Finding 01 · Bedroom 1Flat 602

VISIBLE

Visible light: freshly painted ceiling

THERMAL

Thermal: cool patch 24.6 degrees against 27.2 degrees24.6°C27.2°C
coolwarm

Pin reading vs dry reference

Dry reference 11Reading 41

Likely source

Bathroom floor waterproofing in Flat 702 above

Repair before purchase or possession
  1. Finding 01 · Bedroom 1Repair before purchase or possession
    Location
    Ceiling, 0.6 m from the wall shared with the bathroom
    Area affected
    About 1.8 m x 0.9 m, the size of a door
    Surface temperature
    24.6°C against 27.2°C on the reference wall

    Pin reading vs dry reference

    Dry reference 11Reading 41
    Reasoning
    Patch sits directly below the upstairs bathroom floor trap; adjoining walls read dry; paint above the patch is newer than the rest of the ceiling.
    Next step
    Ask the seller to get the bathroom in Flat 702 repaired before registration, then book a re-scan.
  2. Finding 02 · Living roomRepair before use
    Location
    West wall, below the window sill, both corners
    Area affected
    Two strips about 40 cm wide
    Surface temperature
    25.9°C against 27.2°C on the reference wall

    Pin reading vs dry reference

    Dry reference 11Reading 29
    Reasoning
    High readings only at the sill corners on the rain-facing side; the wall between them reads near the reference.
    Next step
    Ask the seller to reseal the frame and check the sill slope before the next rain.
  3. Finding 03 · KitchenRepair before use
    Location
    Wall behind the sink, 30 cm above the counter
    Area affected
    About 50 cm x 30 cm
    Surface temperature
    26.4°C against 27.2°C on the reference wall

    Pin reading vs dry reference

    Dry reference 11Reading 23
    Reasoning
    Patch follows the concealed drain route; reading rises after the tap runs for five minutes.
    Next step
    Ask for the sink drain joint to be checked by a plumber; re-scan after the repair.
  4. Finding 04 · Bedroom 2Monitor
    Location
    External wall corner behind the wardrobe position
    Area affected
    About 30 cm x 60 cm
    Surface temperature
    26.8°C against 27.2°C on the reference wall

    Pin reading vs dry reference

    Dry reference 11Reading 17
    Reasoning
    Mildly raised readings at the corner only, black spots on the surface, no pattern from outside; room humidity high with windows shut.
    Next step
    Keep a gap behind the wardrobe and ventilate; check again after the monsoon.
  5. Finding 05 · BalconyRepair before use
    Location
    Floor near the drain and the skirting below the door
    Area affected
    Skirting strip about 1 m
    Surface temperature
    26.1°C against 27.2°C on the reference wall

    Pin reading vs dry reference

    Dry reference 11Reading 26
    Reasoning
    Water stands about 1 m from the drain after a bucket test; skirting reads high only on the doorway side.
    Next step
    Ask the seller to correct the slope or seal the door threshold before you move in.

3 · Not accessible

What we could not see.

  • Bathroom 2 walls behind full-height tiles: pinless readings only, limited depth
  • Master wardrobe interior: locked by the seller, not scanned
  • Terrace: not applicable (6th of 11 floors)

4 · Conditions on the day

Conditions on the day of the visit
DateSaturday 9 August 2026
Time on site10:05 to 11:40
Weather, past 7 daysRain on 5 of the past 7 days
IndoorIndoor RH 71%, 27.4°C
Dry reference wallInternal partition, living room to bedroom 2
Reference readingsPin 11 · pinless 14 (relative scale)
InspectorInspector SS-PN-014 (ID shown, booking code matched)

Readings are relative comparisons within this flat, not a laboratory moisture content. Findings are the inspector's opinion on the date of the visit. This report is not a structural survey, a valuation or legal advice.